Page 20 - Fluke Accessory Catalog
P. 20
i400
Fluke current clamps extend the current ranges of digital multimeters, power quality analyzers, and oscillo- scopes and are available for both
ac and ac/dc environments. Most clamps are made with a soft, non- slippery overmold handle to prevent accidental touching of live wires.
For more information on using clamps, visit www.fluke.com/clamp-howto.
Current clamps: AC
20
AC current clamp specifications
i5s
i200
i200s
i400
i400s
i800
i1000s
i3000s
AC range
10 mA to 6 A
1 A to 200 A
1 A to 200 A
1 A to 400 A
0.5 A to 400 A
0.1 A to 600 A
0.2 A to 1000 A
1 A to 3000 A
Accuracy
10 mA to 1 A 1% + 5 mA
1 A to 5 A 1 %, 48 Hz to 65 Hz
< 3 % +0.5 A 48 Hz to 65 Hz
< 1 % +0.5 A 48 Hz to 65 Hz
2 % + 0.06 A 45 Hz to 400 Hz
.5 A to 40 A,
2 % + .015 A, 5 A to 400 A, 2 % + .04 A, 45 Hz to 400 Hz
± 2 % of rdg., 50 Hz to 1 kHz ± 3 % of rdg., (typical)
30 Hz to 50 Hz and 1 kHz to 10 kHz
0.2 to 10 A:
3 % + 0.1 A 10 A to 100 A: 2 % + 0.5 A 100 A to 1000 A: 1%+1A
48 Hz to 65 Hz
1 A to 30 A:
2 % + 0.1 A 1 A to 300 A: 2 % + 0.5 A 1 A to 3000 A: 2%+2A 48 Hz to 65 Hz
Bandwidth (-3 dB)
40 Hz to 5 kHz
40 Hz to 40 kHz
40 Hz to 40 kHz
5 kHz to 20 kHz
5 Hz to 10 kHz
30 Hz to 10 kHz
5 Hz to 100 kHz
10 Hz to 100 kHz
Maximum conductor dia.
15 mm (0.59 in)
20 mm (0.8 in)
20 mm (0.8 in)
32 mm (1.25 in)
32 mm (1.25 in)
54 mm (2.13 in)
54 mm (2.13 in)
64 x 100 mm (2.52 in x 3.94 in)
Maximum conductor size
2 AWG
300 MCM
300 MCM
750 MCM
750 MCM
2-500 MCM or 1-1000 MCM
2-500 MCM or 1-1000 MCM
64 mm (2.52 in)
Output levels
400 mV/A
1 mA/A
10 mV/A 100 mV/A
1 mA/A
10 mV/A 1 mV/A
1 mA/A
1 mV/A 10 mV/A 100 mV/A
10 mV/A 1 mV/A 0.1 mV/A
Output cable
2.5 m to BNC termination
1.5 m shrouded banana plugs
2 m to BNC termination
1.5 m shrouded banana plugs
2.5 m to BNC termination
1.6 m shrouded banana plugs
1.6 m to BNC termination
2.1 m to BNC termination
Warranty
One-year
One-year
One-year
One-year
One-year
One-year
One-year
One-year
Safety rating
CAT III 600 V
CAT III 600 V
CAT III 1000 V CAT IV 600 V
CAT III 1000 V CAT IV 600 V
CAT III 600 V
CAT III 600 V
CAT III 600 V
i430-flex
i2000 flex
i3000s flex-24/i3000s flex-36
i6000s flex-24/i6000s flex-36
AC range
30 A to 3000 A
2 A to 2000 A
3 A to 3000 A
6 A to 6000 A
Accuracy
± 1 % of reading at 25 °C, 50 Hz
± 1 % of range 45 Hz to 65 Hz Ranges: 20 A, 200 A, 2000 A
± 1 % of range, 45 Hz to 65 Hz, Ranges: 30 A, 300 A, 3000 A
± 1 % of range, 45 Hz to 65 Hz, Ranges: 60 A, 600 A, 6000 A
Bandwidth (-3 dB)
10 Hz to 7 kHz
10 Hz to 20 kHz
10 Hz to 50 kHz
10 Hz to 50 kHz
Maximum conductor dia.
177 mm (7 in)
177 mm (7 in)
177 mm (7 in) or 265 mm (10.4 in)
177 mm (7 in) or 265 mm (10.4 in)
Maximum conductor size
610 mm (24 in) circumference
610 mm (24 in) circumference
610 mm (24 in) circumference
610 mm (24 in) circumference
Output levels
85 mV at 1000 A rms, 50 Hz
100 mV/A, 10 mV/A, 1 mV/A
100 mV/A, 10 mV/A, 1 mV/A
50 mV/A, 5 mV/A, 0.5 mV/A
Output cable
2.5 m to BNC termination
2 m with double shrouded banana plugs
2.1 m to BNC termination
2 m to BNC termination
Battery life
No battery
400 hours
400 hours
Warranty
One-year
One-year
One-year
One-year
Safety rating
CAT II 1000 V, CAT III 600 V, CAT IV 300 V
CAT III 600 V
CAT III 600 V
CAT III 600 V