Fluke 1730 Three-Phase Electrical Energy Logger
Designed specifically for energy conscious cus- tomers like you, the Fluke 1730 Three-Phase Electrical Energy Logger introduces a new simplicity to discovering sources of electrical energy waste. Profiling energy usage across your facility helps you identify opportunities for energy savings and provides you with the easy-to-understand data required for you to take the right action.
• Quickly understand specific points of energy loss, reduce energy bills more easily than ever
• Optimized layout with specialized touch screen makes navigation easy—even with gloves on
• Advanced auto-correct feature eliminates costly errors due to improper connections
• Power directly from the measured voltage
line (up to 500 V) or with conventional ac power cord
Measurement modes
Voltage, current, frequency, active power, apparent power, reactive power, power factor, total harmonic distortion (THD), energy.
Specifications
Accuracy
Parameter
Range
Resolution
Intrinsic accuracy at reference conditions (% of reading + % of full scale)
Voltage
1000 V
0.1 V
± (0.2 % + 0.01 %)
Current: Direct input
iFlex1500-12
150 A
0.1 A
± (1 % + 0.02 %)
1500 A
1A
± (1 % + 0.02 %)
iFlex3000-24
300 A
1A
± (1 % + 0.02 %)
3000 A
10 A
± (1 % + 0.02 %)
iFlex6000-36
600 A
1A
± (1.5 % + 0.03 %)
6000 A
10 A
± (1.5 % + 0.03 %)
i40s-EL clamp
4A
1 mA
± (0.7 % + 0.02 %)
40 A
10 mA
± (0.7 % + 0.02 %)
Frequency
42.5 Hz to 69 Hz
0.01 Hz
± (0.1 %)
Aux input
± 10 V dc
0.1 mV
± (0.2 % + 0.02 %)
Intrinsic uncertainty ± (% of reading + % of range)1
Parameter
Influence quantity
iFlex1500-12
iFlex3000-24
iFlex6000-36
i40s-EL
150A/1500A
300A/3000A
600/6000A
4A/40A
Active power P
PF ≥ 0.99
1.2 % + 0.005 %
1.2 % + 0.0075 %
1.7 % + 0.0075 %
1.2 % + 0.005 %
0.5 250 V
0.015 %
0.0225 %
0.0225 %
0.015 %
1Range = 1000 V x Irange
Reference conditions:
Environmental: 23 °C ± 5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65 % Input conditions: Cosφ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10 %.
Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V
Input current: I > 10 % of Irange
Primary conductor of clamps or Rogowski coil in center position
Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C
Ordering information
Included accessories
Models
1730 Energy Logger, power supply, voltage test lead, dolphin clip, i1730-flex 1500iFlex Flexible Current Probes, color-coded wire clips, power cord, test lead set with stackable plugs, test lead set with stackable plugs, DC power cable(s), USB cable A, mini USB, soft storage bag, input connector decal, documentation info pack.
1730/BASIC Three-Phase Electrical Energy logger (excludes current probes)
1730/US Portable Energy Logger US version
1730/EU Portable Energy Logger EU version
1730/INTL Portable Energy Logger ITNL version
For more information, go to www.fluke.com/pq
Power Quality Analyzers
31
Energy Analyze Software
Download, analyze and create automated reports to get a complete picture of the energy savings potential. With Energy Analyze you can compare multiple data points over time, with intuitive graphical controls and report writing capabilities, which is the first step to reducing the cost of your energy bill.
Applications
The Fluke 1730 Energy Logger can be used for conducting energy surveys that require both a voltage and current connection. In addition, load studies that require a current connection only (when a voltage connection is either difficult to make or unnecessary) for evaluating electrical demand capacity can also be performed.